Circuit breakers are built for voltage
ratings as defined in IEEE C37.042 and IEEE C37.063. They have to be
dimensioned to withstand the maximum voltages as specified. The rated
maximum voltage is the upper limit for operation.
For circuit breakers rated in
accordance with ANSI C37.06-19874 (or earlier), the range between
upper and lower limit is defined by voltage range factor K.
Current-interrupting capabilities vary within this range in inverse
proportion to the operating voltage.
For circuit breakers rated in
accordance with ANSI C37.06-19974 (or later), the
current-interrupting capability is a constant Ka value at any voltage
equal to or lower than the rated maximum voltage.
The insulation level is determined by
the rated withstand test voltages specifying the low frequency
voltage (kV, rms) and the impulse voltage (kV, crest). High-voltage
breakers must essentially withstand switching surges and both full
and chopped-wave lightning impulses.
For multiple-break circuit breakers,
equal voltage distribution over the series breaks is achieved by
grading capacitors paralleled to the interrupting chambers.
Coordination between inner and outside insulation, as well as
insulation coordination between interrupters and ground insulation,
has to be properly designed to prevent flashover inside the breaker
or over the open break.
Outdoor breakers are generally
available with special bushings that provide increased creepage
distance for installation sites with highly contaminated air. For
heavily polluted atmospheres, spray washing of live or deenergized
breakers may be an additional measure.
Because of the method of design with
enclosed ground insulation, the GIS circuit breaker is not influenced
by atmospheric pollution. For installation at altitudes above 3300 ft
(1000 m), altitude correction factors have to be applied.
The values of rated maximum voltages
and insulation levels are multiplied by these factors to obtain the
values for the application. The altitude correction factors are as
listed in ANSI/IEEE C37.04-1979.
Correction factors are under discussion
in an IEEE Switchgear committee working group and are expected to
change. These factors will be published in IEEE C37.100.15.
Particular reference is made to the rating structures and preferred
ratings for ac high-voltage circuit breakers per the latest standard
revisions of IEEE C37.042 and IEEE C37.063.
No comments:
Post a Comment