STEAM TURBINE LOSSES BASIC INFORMATION



Clearance leakage. A 100% efficiency cannot be obtained because of friction in the blading and clearance between the stationary and rotating parts, and because the nozzle angle cannot be zero degrees.

Axial clearance increases in the stages further from the thrust bearing to satisfy the need to maintain a minimum clearance at extreme operating conditions when the differential expansion between the light rotor and heavy casing is at its worst.

To reduce this leakage, radial spillbands are used. These thin, metal-strip seals may be attached to the diaphragm or casing and extend close to the shroud bands covering the rotating blades.

This clearance can be kept quite close (0.020 to 0.060 in), and axial changes in the rotor position do not affect the clearance since the important on reaction stages with small blade heights because of the pressure drop across the moving blades.

Nozzle leakage. Leakage around the nozzles between the bore of the blade ring or nozzle diaphragm and the drum or rotor must be kept to a minimum.

This leakage is controlled through the use of a metallic labyrinth packing which consists of a single ring with multiple teeth arranged to change the direction of the steam as well as to minimize the leakage area.

Labyrinth packings are also used at the shaft ends to step the pressure down at the high-pressure end and to seal the shaft at the vacuum end.

Rotation loss. Rotation of the rotor consist of losses due to the rotation of the disks, the blades, and shrouds. Partial-arc impulse stages have a greater windage loss within the idle buckets. Rotation losses vary directly with the steam density, the fifth power of the pitch diameter, and the third power of the rpm.

In general, the windage loss amounts to less than 1% of stage output at normal rated output. At no-load conditions, windage loss for noncondensing turbines approximates 1.5% of the rating per 100 lb/in2 exhaust pressure, and on condensing units approximates from 0.4% to 1.0% of the rating at 1.5 inHg (abs) exhaust pressure.

Carryover loss. A carryover loss (about 3%) occurs on certain stages when the kinetic energy of the steam leaving the rotating blades cannot be recovered by the following stage because of a difference in stage diameters or a large axial space between adjacent stages.

Typically, this happens in control stages and in the last stages of noncondensing sections. The last stages of condensing turbines have the largest carryover losses (normally referred to as exhaust loss) because of the large variations in exhaust volumetric flow with exhaust pressure and the large variation of stage pressure ratio with load.

Stages preceding the last operate with essentially a constant pressure ratio down to very low loads and consequently can be designed for peak efficiency at a wide range of loads.

Leaving loss. Condensing turbines are frequently “frame sized” by last-stage blade height. It is sometimes economical to size the unit with exhaust loss equal to 5% deterioration in overall turbine performance at the design point (valves wide-open throttle flow and 1.5 inHg [abs] exhaust pressure) when the normal expected exhaust pressure will be higher or the unit will be operating at part load for a large part of the time.

Nozzle end loss, partial arc. Control stages and partial-arc impulse stages are subject to end losses at the interface of the active and inactive portions of the blading as the stagnant steam within the idle bucket passages enters the active arc of nozzles and must be accelerated.

There is also a greater turbulence in the steam jet at both ends of the active arc. In partial-arc impulse stages, the increase in efficiency due to larger blade heights (aspect ratio) is partially offset by increased rotation and end losses, and there is an optimum to this proportioning beyond which there is an overall loss.

Supersaturation and moisture loss. Moisture in the steam causes supersaturation and moisture losses in the stage. The acceleration of the moisture particles is less than that of the steam, causing a momentum loss as the steam strikes the particles.

The moisture particles enter the moving blades (buckets) at a negative velocity relative to the blades, resulting in a braking force on the back of the blades. Supersaturation is a temporary state of supercooling as the steam is rapidly expanded from a superheated state to the wet region before any condensation has begun.

The density is greater than when in equilibrium, resulting in a lower velocity as the steam leaves the nozzle. As soon as some condensation occurs at approximately 3.5% moisture, according to Yellot, a state of equilibrium is almost instantly achieved and supersaturation ceases.

TURBINE GENERATOR STANDARD AND OPTIONAL EQUIPMENT



Standard Equipment
The manufacturer shall equip the turbine-generator unit with the following standard equipment:

1) Speed/Load-Control System.
A speed /load-control system capable of controlling and regulating the speed of the turbine in conformity with the performance characteristics hereinafter specified. The speed/load-control system should include means by which the steady-state speed regulation may be adjusted to values within the limits hereinafter specified.

Adjustment of the steady-state speed regulation, while the turbine is in operation, is not required by this recommended practice unless otherwise agreed upon between the manufacturer and the purchaser.

2) Speed/Load Reference Changer.
A speed/load changer by means of which the speed or power output of the turbine may be changed within the limits hereinafter specified while the turbine is in operation. The speed/load reference changer shall be equipped with means for manual adjustment and should be equipped to accept input(s) for remote control.

3) Valve Position Limiter (Load Limit).
For turbines rated over 10 MW, a valve position limiter manually adjustable to limit the degree of opening of the control valves to any value within the full range of valve travel while the turbine is in operation.

If this device is used for load-limiting purposes, the speed-control system will not necessarily control the overspeed of the turbine, if the speed/load reference changer is set at its high-speed stop.

4) Miscellaneous.
At the discretion of the manufacturer, any instruments, controls, or safety devices not specified as standard equipment in (1), (2), and (3) may be included.

Optional Equipment
The following devices or other optional devices may be specified by the purchaser:

1) Valve Position Limiter.
For turbines rated 10 MW or under, a valve position limiter.

2) Adjustment of Steady-State Regulation.
A means by which, in the speed/load-control system the steady-state speed regulation may be adjusted, within limits agreed to by the manufacturer and purchaser, while the turbine is operating at any power output.

3) Remote or Local Indication.
A means for remote or local indication, or both, of the positions of the control valves or any other element of the control system to be specified by the purchaser.

4) Remote Control of the Valve Position Limiter.
For turbines rated over 10 MW, a means for remote setting of the valve position limiter within the limits hereinafter specified.

5) Remote Control of Speed/Load Reference Changer.
For turbines rated over 10 MW, a means for remote control of the speed/load reference changer within the limits hereinafter specified.

6) Miscellaneous.
At the discretion of the manufacturer, any instruments, controls, or safety devices not previously specified as optional equipment may be included.