VOLTAGE RATING AND ISULATION OF POWER CIRCUIT BREAKERS BASIC INFORMATION AND TUTORIALS



Circuit breakers are built for voltage ratings as defined in IEEE C37.042 and IEEE C37.063. They have to be dimensioned to withstand the maximum voltages as specified. The rated maximum voltage is the upper limit for operation.

For circuit breakers rated in accordance with ANSI C37.06-19874 (or earlier), the range between upper and lower limit is defined by voltage range factor K. Current-interrupting capabilities vary within this range in inverse proportion to the operating voltage.

For circuit breakers rated in accordance with ANSI C37.06-19974 (or later), the current-interrupting capability is a constant Ka value at any voltage equal to or lower than the rated maximum voltage.

The insulation level is determined by the rated withstand test voltages specifying the low frequency voltage (kV, rms) and the impulse voltage (kV, crest). High-voltage breakers must essentially withstand switching surges and both full and chopped-wave lightning impulses.

For multiple-break circuit breakers, equal voltage distribution over the series breaks is achieved by grading capacitors paralleled to the interrupting chambers. Coordination between inner and outside insulation, as well as insulation coordination between interrupters and ground insulation, has to be properly designed to prevent flashover inside the breaker or over the open break.

Outdoor breakers are generally available with special bushings that provide increased creepage distance for installation sites with highly contaminated air. For heavily polluted atmospheres, spray washing of live or deenergized breakers may be an additional measure.

Because of the method of design with enclosed ground insulation, the GIS circuit breaker is not influenced by atmospheric pollution. For installation at altitudes above 3300 ft (1000 m), altitude correction factors have to be applied.

The values of rated maximum voltages and insulation levels are multiplied by these factors to obtain the values for the application. The altitude correction factors are as listed in ANSI/IEEE C37.04-1979.

Correction factors are under discussion in an IEEE Switchgear committee working group and are expected to change. These factors will be published in IEEE C37.100.15. Particular reference is made to the rating structures and preferred ratings for ac high-voltage circuit breakers per the latest standard revisions of IEEE C37.042 and IEEE C37.063.

LOW VOLTAGE CIRCUIT BREAKER APPLICATION AND RATINGS BASIC INFORMATION



Application.
Air circuit breakers are used on dc and ac circuits for the protection of general lighting, power, and motor circuits. Distinction is made between various protection classes and different service and ambient conditions.

For selection of a breaker, type and rating, operating speed, selectivity with fuses, and high voltage must be taken into account. Further consideration has to be given to severe or hazardous service conditions like tropical climate or marine- or explosion-proof installations. Reference is made to IEEE C37.1313, C37.1414, and C37.1715; UL-48916; and ANSI C37.1617.

Ratings.
Standard electrically and manually operated breakers are listed in ratings up to and including 5000 A ac and 12,000 A dc. Electrically operated breakers are available in higher current ratings for special applications.

Standard breakers are rated on the basis of a temperature rise on the contacts and terminals not to exceed 50 deg C above an ambient of 40#C (class 90 insulation). Voltage ratings are 254 to 635 V ac and 250 to 3200 V dc.

The short-time current ratings are based on 3-phase symmetric short-circuit currents; the singlephase short-circuit current ratings are 87% of these values. For details, refer to the latest revisions of ANSI C37.1617.

Assembly Variations.
The breakers are usually installed in a metal-enclosed cubicle for dead-front or drawout type of construction. Metal barriers between breakers and busbars provide increased safety in service.

Hand operation by means of a lever is common, even on large breakers. Electric operation by means of a solenoid or motor mechanisms for 48, 125, or 250 V dc, or 120 or 240 V ac is obtainable on all but the smallest sizes of breakers.

Breakers are supplied with an overcurrent trip mechanism which may be of the instantaneous or the time-delay type, or a combination of both. Trip devices are adjustable over a wide range of ratings. Other trip devices and arrangements may be used, for example, undervoltage trips, shunt trips connected to overvoltage, reverse current, or overcurrent relays.

Multiple-pole circuit breakers are commonly used in practically all capacities, one pole being used for each ungrounded line of a circuit, that is, a 2-pole breaker for a 3-wire grounded circuit or a single-pole breaker for a 2-wire grounded circuit.

Breakers can usually be equipped with auxiliary contacts, alarm contacts, push-button control, position indicator, and key interlock. The widely used drawout type of breaker may be moved into and locked in the connected, test, and disconnected positions and/or completely withdrawn. Refer to the latest revisions of IEEE C37.1313, C37.1414, and C37.1715, and ANSI C37.1617.

EXCITATION SYSTEM VOLTAGE AND CURRENT SPECIFICATION TUTORIALS



Rated Current
The continuous current rating should be specified to be equal to or larger than the maximum required by the synchronous machine field under any allowed continuous operating conditions. Note that some machines have a continuous overload rating.

In addition, ANSI C50.12-1982 [2], ANSI C50.13-1989 [3], and ANSI C50.14-1977 [4] allow all machines to operate at rated MVA and within ± 5% of rated terminal voltage. Some machines may require an even wider operating range.

The need for off-frequency operation must also be considered in establishing the rating. Some machines, such as combustion-turbine-drive units, have a variable rating depending on ambient air temperature.

The excitation system for these machines may require a variable rating based on ambient air temperature. In the past, some excitation systems have had a small continuous negative current rating. This was utilized when the machine was operated as a synchronous condenser and the negative field current allowed a slightly greater transmission line charging capability.

The negative current was relatively easily supplied from commutator-type exciters, with little additional complexity. Modern exciters employing solid-state rectifiers do not normally have inherent capability for negative currents.

It could be obtained with great complexity, which cannot justify the associated minimal performance improvement (except for synchronous condensers). Some modern exciters will generate a transient negative voltage to force the decay of field current toward zero.

This should not be confused with the concept of a continuous negative current rating, which is mentioned above. For exciters that are specified with redundant current paths or cooling elements, the continuous rating should apply with the redundant parts out of service. The exciter efficiency and losses should be measured at the rated current and voltage point with all redundant parts in service, since this is the normal operating mode.

Rated Voltage
The continuous voltage rating of a system should be such that the voltage is sufficient to supply the necessary continuous current to the synchronous machine field, with the field at its maximum temperature under rated load conditions.

In addition, the continuous voltage capability should allow operation of the synchronous machine at rated MVA and within ±5% of rated terminal voltage unless otherwise specified.

In determining the required voltage for the continuous as well as the transient ratings mentioned later, all voltage drops, including interconnecting bus or cable run voltage drop, up to the field winding terminals should be considered. Any brush drop voltage should be considered part of the synchronous machine field circuit.

SYNCHRONOUS MACHINE TERMINAL VOLTAGE TRANSDUCER AND LOAD COMPENSATOR MODELS TUTORIALS



A block diagram of the terminal voltage transducer and the load compensator is shown in Fig 2. These model elements are common to all excitation system models described in this document.

  Figure 2-Terminal Voltage Transducer and Optional Load Compensation Elements

It is realized that, for some systems, there may be separate and different time constants associated with the functions of voltage sensing and load compensation. The distinction is not recognized in this model, in which only one time constant, TR, is used for the combined voltage sensing and compensation signal.

When load compensation is not employed (RC=XC= 0), the block diagram reduces to a simple sensing circuit. The terminal voltage of the synchronous machine is sensed and is usually reduced to a dc quantity.

While the filtering associated with the voltage transducer may be complex, it can usually be reduced, for modeling purposes, to the single time constant, TR, shown. For many systems, this time constant is very small, and provision should be made to set it to zero.

The terminal voltage transducer output, VC, is compared with a reference that represents the desired terminal voltage setting, as shown on each of the excitation system models. The equivalent voltage regulator reference signal, VREF, is calculated to satisfy the initial operating conditions.

It will, therefore, take on a value unique to the synchronous machine load condition being studied. The resulting error is amplified as described in the appropriate excitation system model to provide the field voltage and subsequent terminal voltage to satisfy the steady-state loop equations.

Without load compensation, the excitation system, within its regulation characteristics, attempts to maintain a terminal voltage determined by the reference signal. When compensation is desired, the appropriate values of RC and XC are entered.

In most cases, the value of RC is negligible. The input variables of synchronous machine voltage and current must be in phasor form for the compensator calculation. Care must be taken to ensure that a consistent per unit system is utilized for the compensator parameters and the synchronous machine current base.

This type of compensation is normally used in one of the following two ways:
1) When units are bused together with no impedance between them, the compensator is used to create an artificial coupling impedance so that the units will share reactive power appropriately. This corresponds to the choice of a regulating point within the synchronous machine. For this case, RC and XC would have positive values.

2) When a single unit is connected through a significant impedance to the system, or when two or more units are connected through individual transformers, it may be desirable to regulate voltage at a point beyond the machine terminals.

For example, it may be desirable to compensate for a portion of the transformer impedance and effectively regulate voltage at a point part way through the step-up transformer. For these cases,
RC and XC would take on the appropriate negative values.

Some compensator circuits act to modify terminal voltage as a function of reactive and real power, instead of reactive and real components of current. Although the model provided will be equivalent to these circuits only near rated terminal voltage, more precise representation has not been deemed worthwhile.  

BRUSH POTENTIAL CURVES OF DIRECT CURRENT GENERATORS BASIC INFORMATION



When a dc machine develops some commutation sparking, the user may suspect that the commutating-pole air gap is not set correctly.

“Brush potential curves” are often taken to prove or disprove such suspicions. These are taken by measuring the voltage drops between the brush and commutator surface at four points while the machine is operating at constant speed and load current (see Fig. 8-34).



The voltages at 1, 2, 3, and 4 are taken by touching the pointed lead of a wooden pencil to the commutator surface. The circuit is completed with leads and a low-reading voltmeter is shown.

The voltages are then plotted. A curve such as A of Fig. 8-34 may indicate undercompensation due to a too large commutating-pole gap. Curve C may indicate overcompensation with too much flux density in the commutating-pole air gap.

Curve B is typical of good compensation. Justification for such conclusions is based on the theory that best commutation (coil current reversal) will be linear while the coil passes under the brush.

This is possible only if there are no circulating currents. Undercompensation should cause circulating currents that would crowd the current to the leaving edge of the brush and cause a high voltage at point 4.

Overcompensation would reverse the current too soon and would actually reverse the voltage drop at point 4. Even to an expert, this test is only an indicator that more definitive tests, such as a buck-boost test, are needed.

Many other factors, including brush riding, commutator surface conditions, and sparking, influence the readings. Where machine changes may be required, the manufacturer should be consulted.

EXCITATION SYSTEM CEILING VOLTAGE OF SYNCHRONOUS GENERATORS



Fast control of excitation current is needed to preserve SG transient stability and control its voltage. Higher ceiling excitation voltage, corroborated with low electrical time constants in the excitation system, provides for fast excitation current control.

Today’s ceiling voltages are in the range of 1.6 to 3.0 P.U. There is a limit here dictated by the effect of magnetic saturation, which makes ceiling voltages above 1.6 to 2.0 P.U. hardly practical.

This is more so as higher ceiling voltage means sizing the insulation system of the exciter or the rating of the static exciter voltage for maximum ceiling voltage at notably larger exciter costs.

The debate over which is best — the alternating current (AC) brushless exciter or static exciter (which is specified also with a negative ceiling voltage of –1.2 to 1.5 P.U.) is still not over.

A response time of 50 msec in “producing” the maximum ceiling voltage is today fulfilled by the AC brushless exciters, but faster response times are feasible with static exciters.

However, during system faults, the AC brushless exciter is not notably disturbed, as it draws its input from the kinetic energy of the turbine-generator unit.

In contrast, the static exciter is fed from the exciter transformer which is connected, in general, at SG terminals, and seldom to a fully independent power source.

Consequently, during faults, when the generator terminal voltage decreases, to secure fast, undisturbed excitation current response, a higher voltage ceiling ratio is required.

Also, existing static exciters transmit all power through the brush slipring mechanical system, with all the limitations and maintenance incumbent problems.

VOLTAGE – CURRENT AND POWER IN A CIRCUIT WITH COMBINED RESISTANCE AND INDUCTANCE BASIC AND TUTORIALS



Apparent Power
The practical significance of apparent power is as a rating unit. For example, an ac generator supplies apparent power at essentially constant voltage and frequency. Its output capacity is then described in Mega Volt Amps (MVA).

Transformer and motor capacities are also rated in MVA or KVA for similar reasons. Although the utility must provide apparent power, it receives direct compensation only for active power utilised by its customers.

The ratio of active to apparent power is therefore, an important quantity and is defined as the power factor. This number can range from zero to one but good economics requires it to be as close to unity as possible.

It can be thought of as a measure of the system’s effectiveness in using apparent power to do useful work. The terminology can be in any one of the following forms:

Power Factor = PF
= Real Power/Apparent Power
= Watts/ Volt Amps

Note: There is a time lag between the apparent power and real power. This corresponds to the time lag between voltage and current for reactive loads.

For capacitive loads, we have a leading power factor.

For inductive loads, it is lagging. Power Factor Angle is a measurement that describes how close the apparent power is to being totally real or supplying a pure resistive load. The Power Factor rating can be summarized in two main areas:

• Efficiency: The lower the power factor, demanded by the load which requires a given amount of active power, the greater the size of line current that has to be supplied by the generator and sent through the transmission system. This means higher winding and line losses and reduced efficiency;

• Voltage Regulation: The lower the power factor and the greater the generator current, the greater the reactance voltage drops along the line. This means a lower voltage at the load and, consequently, poorer system voltage regulation.

The relationship between apparent, active and reactive power is that of a right-angled triangle.


The following relationships exist between voltage, current, apparent power (U), active power (P) and reactive power (Q).
U^2 = P^2+Q^2
U = VI
P = VI cosθ
Q = VI sinθ
The power factor is equal to cosθ