THREE PHASE SYSTEM AND PHASE SEQUENCE BASIC AND TUTORIALS


The major portion of all electric power presently used in generation, transmission, and distribution uses balanced three-phase systems. Three-phase operation makes more efficient use of generator copper and iron.

Power flow in single-phase circuits was shown in the previous section to be pulsating. This drawback is not present in a three-phase system. Also, three-phase motors start more conveniently and, having constant torque, run more satisfactorily than single-phase motors.

However, the complications of additional phases are not compensated for by the slight increase of operating efficiency when polyphase systems other than three-phase are used.

A balanced three-phase voltage system is composed of three single phase voltages having the same magnitude and frequency but time-displaced from one another by 120°.

Figure 2.5(a) shows a schematic representation where the three single-phase voltage sources appear in a Y connection; a Δ configuration is also possible. A phasor diagram showing each of the phase voltages is also given in Figure 2.5(b).


Phase Sequence
As the phasors revolve at the angular frequency ω with respect to the reference line in the counterclockwise (positive) direction, the positive maximum value first occurs for phase a and then in succession for phases b and c.



Stated in a different way, to an observer in the phasor space, the voltage of phase a arrives first followed by that of b and then that of c. The three-phase voltage of Figure 2.5 is then said to have the phase sequence abc (order or phase sequence or rotation are all synonymous terms).

This is important for applications, such as three-phase induction motors, where the phase sequence determines whether the motor turns clockwise or counterclockwise.

With very few exceptions, synchronous generators (commonly referred to as alternators) are three phase machines. For the production of a set of three voltages phase-displaced by 120 electrical degrees in time, it follows that a minimum of three coils phase-displaced 120 electrical degrees in space must be used.

It is convenient to consider representing each coil as a separate generator. An immediate extension of the single-phase circuits discussed above would be to carry the power from the three generators along six wires.

However, instead of having a return wire from each load to each generator, a single wire is used for the return of all three. The current in the return wire will be Ia + Ib + Ic; and for a balanced load, these will cancel out. If the load is unbalanced, the return current will still be small compared to either Ia, Ib, or Ic.

Thus the return wire could be made smaller than the other three. This connection is known as a four wire three-phase system. It is desirable for safety and system protection to have a connection from the electrical system to ground. A logical point for grounding is the generator neutral point.

2 comments:

  1. I am really happy with your blog because your article is very unique and powerful for new reader.Dc Capacitor

    ReplyDelete
  2. Nice post with informative and good quality content. Thank you for sharing this information with us. This is really helpful. Also check lighting panel

    ReplyDelete

PREVIOUS ARTICLES

free counters